Enter your rooms and NCC climate zone to instantly calculate your home's cooling load and find the right ducted air conditioner size — in kW and L/s. No sign-up, no cost, no download.
This tool uses the W/m² load factor method recommended in AIRAH DA07 for preliminary residential sizing. Each room's floor area is multiplied by a climate-zone-specific cooling load factor (W/m²) to give a sensible heat load. Dividing the total wattage by 45 W per L/s gives the required airflow, and the tool then matches the smallest ducted unit whose rated airflow meets or exceeds your total.
This approach is accurate for standard residential homes with typical insulation and glazing. For homes with high glazing ratios, concrete slab construction, or unusual orientations, use neuralduct's full design tool which lets you adjust load factors room by room.
The W/m² figures are rule-of-thumb values calibrated to Australian residential conditions — they account for solar gain, internal loads, and typical ventilation rates for each climate type.
| Zone | Description | Key cities | W/m² |
|---|---|---|---|
| 1 | Hot Humid | Darwin, Cairns, Broome | 160 |
| 2 | Warm Humid | Brisbane, Townsville, Gold Coast | 145 |
| 3 | Hot Dry | Alice Springs, Broken Hill, Kalgoorlie | 145 |
| 4 | Mixed Dry | Mildura, Griffith, Dubbo | 130 |
| 5 | Mild Temperate | Sydney, Perth, Adelaide, Canberra | 125 |
| 6 | Cool Temperate | Melbourne, Hobart, Ballarat | 110 |
| 7 | Cool | Canberra, Armidale, Cooma | 100 |
| 8 | Sub-Alpine | Perisher, Thredbo, Falls Creek | 95 |
Once you know the total L/s, the next step is to size the ductwork. AS 4254.2 sets velocity limits for each duct diameter — for example, Flex 300mm duct is limited to 140 L/s. Sizing ducts correctly ensures quiet operation, low friction losses (NCC J6 requires ≤ 1.0 Pa/m on the index run), and even airflow to each room.
neuralduct's full design tool does all of this automatically: auto-sizes every duct, validates velocities in real time, checks the friction rate on every segment, and flags any AS 1668.2 fresh air shortfalls — so you can hand over a compliant design in minutes instead of hours.
Use the pre-filled calculators below for your city: